EMF equation of transformer is very important for understanding the working of the transformer. When a sinusoidal voltage is applied to the primary of the transformer it draws magnetizing current to set up flux in the core.
The flux links to the secondary and produces EMF. We can easily derive the EMF equation of the transformer by calculating the rate of change of the flux in one cycle of the AC waveform. Induced EMF in the primary and secondary of the transformer also depends on the turn ratio of the transformer.
The ratio of secondary EMF to primary EMF is called the voltage transformation ratio of the transformer. The ratio of primary turns to secondary turns is called the transformer turns ratio(TTR).
The flux set up in the core gets linked to the primary and secondary winding of the transformer. The alternating flux set up in the core when linked to turns of the primary and secondary winding induces voltage called EMF.
The EMF induced in the transformer winding depends on the number of turns and the rate of change of the flux. The EMF induced across the primary and secondary always opposes the applied voltage.
According to Faraday’s law of electromagnetic induction, if the alternating flux links to a coil the voltage is induced in the coil. The voltage induced in the primary and the secondary winding of the transformer is as given below. The RMS value of secondary induced EMF and primary induced EMF can be calculated using Faraday’s law of electromagnetic induction.
Where,
The minus sign shows that the voltage induced in the primary and secondary opposes the applied voltage.
Derivation of EMF Equation Of Transformer
The derivation of the EMF equation of the transformer can be derived by calculating the rate of change of the flux in the transformer core. The flux set up in the core is sinusoidal.
The flux in the core changes from + Фm to -Фm in 1/2f seconds.
The voltage induced in the primary is
The flux induced in the primary is because of the sinusoidal voltage applied to the primary so the flux also varies in a sinusoidal manner. The instantaneous value of the flux in the transformer is ;
Putting the value of flux in the equation (1)
The maximum value of voltage induced in the primary is
The root mean square (RMS) value of the induced voltage in the primary
Putting the Ep(max) value in equation(4)
Similarly, the root mean square (RMS) value of the induced voltage in the secondary is ;
The general EMF Equation of the transformer is;
Voltage Transformation Ratio of Transformer
The ratio of the secondary turns to primary turns is known as the voltage transformation ratio of the transformer and it is denoted by the letter ‘K’.
Dividing equation(6) by equation(5)
If the secondary turns are more than the primary turns, the secondary voltage will be higher than the primary voltage and the turns ratio (K) is greater than 1. The transformer that has a voltage transformation ratio of more than 1 is called a step-up transformer.
If the voltage transformation ratio (K) is less than 1, the transformer is called a step-down transformer.
The magnetizing MMF is negligible when substantial current flows in the primary and secondary winding of the transformer. The total MMF of the primary and secondary MMF is equal to the magnetizing MMF. The transformer is a constant flux machine as long as voltage and frequency remain constant.
When the transformer is substantially loaded, the magnetizing MMF can be neglected.
The negative sign shows that the current in the primary and secondary winding are in opposite direction with respect to the magnetizing current. The minus sign can be dropped for the calculation of the transformer transformation ratio.
From equations (7) & (8)
Here, K is the voltage transformation ratio of the transformer.
The voltage transformation ratio equation (9) of the transformer is true if the flux in the transformer core is constant. The flux in the transformer changes if the supply voltage and or frequency gets deviates from its designed value.
Transformer Turns Ratio
The ratio of primary(Np) to secondary turns(Ns) of the transformer is known as the transformer turns ratio or TTR. It is denoted by the letter ‘a’.
Now, we can write the turn ratio and voltage transformation equations as;
Solved Problems on transformer EMF equation
A two-winding transformer has primary winding with 300 turns and secondary winding with 10 turns. The primary winding is connected to a 3300 V supply system. Calculate-
- The secondary voltage at no load
- Primary current when the 100-amp load is connected to secondary
- Apparent power flowing in the primary and secondary circuit
- Turns ratio and voltage transformation ratio of transformer?
First transformer law:
The secondary voltage at no load:
The secondary voltage at no load= 110 Volts
Second transformer law:
Primary current when the 100-amp load is connected to secondary
Primary current = 3.33 Amperes
Apparent power in the primary circuit
Apparent Power in the secondary circuit
Transformer turns ratio(TTR)
Transformer voltage transformation ratio